top of page
ACWindings.gif
Search
ACW

Sometimes, an original winding need to be redesigned


Sometimes, an original winding need to be redesigned.

Why?

Here is an example.

It is about the 4-pole motor of 200 kW; 400 V; Delta connected ( see the photo of nameplate).

Original winding data are:

- double-layer lap winding,

- pitch 1-14,

- 60 slots,

- 4-Delta connection,

- 12 groups of 5 coils,

- 6 groups with 7,8,7,8,7 t/c and 6 groups with 8,7,8,7,8 t/c.

Motor has a repetitive premature failures despite the fact that average lifetime of such a motor should be about 30 years ( with regular maintenance).

At first glance the cause is obvious.

It is weak design from start because of two things:

- excessive value of volts per coil ( approx. 85 Volts) caused with 4D connection,

- different numbers of turns per parallel path: 37 and 38 turns/path will cause a circulating currents and overheating a half of parallels paths.

If the manufacturer's data are repeated during repair, whether the guarantee can be requested or given?

What should be done in such a case?

First of all, send us all the core & slot dimensions in order to check the core capabilities and find out whether or not an option with two circuits is possible..

If there is a possibility, then you should get approval for the redesign from customer.

SOON: Another example of bad manufacturer's design.


(Consulting Agency)
bottom of page